DN15-DN40 BTU Meter/Ultrasonic Heat Meter Cooling and Heating Measuring ULTB-15~40

The temperature range is 4~95℃.

Measurement unit: Kwh, Gcal, GJ

Communication Interface choice:

1. M-BUS

2. RS-485

3. Pulse output

4. LoRa/LoRaWAN( 868 MHz)

5. Water Meter Impulse output, connects Heat Meter, M-BUS/RS-485 output

6. NB-IoT

BTU Meter & Energy Measurement

BTU meters are engineered for precision measurement across diverse systems such as:


• Heating, Ventilation, and Air Conditioning(HVAC)

• Building Management Systems (BMS)
• Domestic Hot Water (DHW)
• District Cooling Systems (DCS)
• District Energy Systems (DES)
• Industrial & Commercial (I&C) applications etc.


Models and Specifications

Model
Qn
(m3/h)
Length
(mm)
DN
(mm)
Sensor lengthDisplayCommunication interfaceClass
ULTB-15-0.60.6110151.5mKwh, Gcal , GJ1.M-BUS 2.RS-485 3.Pulse output 4. LoRa/ LoRaWAN 5.Water Meter Impulse output, connects Heat Meter, M-BUS/RS-485 output.2
ULTB-15-1.51.511015
ULTB-202.513020
ULTB-253.516025
ULTB-32618032
ULTB-401020040


Features:

1. Lithium battery life: 10 years

2. Archive: 38 Month data historical( M-BUS, RS-485, Pulse output )

3. Installation choice: Water supply pipeline or Water return pipeline
4. Horizontal or Vertical installation
5. Accuracy: Class 2, meets EN1434
6. Measuring range (q s/q i =100:1)
7. Temperature sensor: PT 1000
8. Environment standard Class: A
9. Min. temperature difference: 3℃

10. Water pressure: ≤1.6Mpa


Main Technical Parameters:

Normal DNmm151520253240
Qnm3/h0.61.52.53.5610
Qmaxm3/h1.23571220
Qminm3/h0.0120.030.050.070.120.2
Body thread----G¾"BG¾"BG1"BG1¼"BG1½"BG2"B
Connection thread----½"½"¾"1"1¼"1½"
Heightmm858595105105115
Lengthmm110110130160180200
Pressure loss≤0.02MPa


Temperature sensor pair: PT 1000




Installation